The North America market website will be available by November 2025. After clicking the 'Update' button, you will be redirected to the legacy version of the website. Le site Web du marché nord-américain sera disponible d'ici novembre 2025. Après avoir cliqué sur le bouton « Mettre à jour », vous serez redirigé vers le legacy version du site Web.
Update Update

PY68

Downloads

Colour

Technical Data

last update: 04/11/2025
Description
Logic controller for automation solutions based on KNX protocol. This allows small and medium-sized systems to be automated with an architecture including KNX and a DALI control via an appropriate gateway. The controller is also suitable for large systems with a BMS-operated architecture including KNX and DALI. The logic controller can be used as a gateway to translate and consent communication between different system components and as an aggregator for saving, analysing and sending data. It can also be used as a user interface for displaying relevant information on mobile devices and as an event controller that sends e-mails in case of problems.
Applications:
-Logic functions.
-WEB SCADA display for PCs and touch devices.
-Cross-standard Gateway between KNX and Modbus RTU/TCP.
-BACnet Server (500 points).
-Integration with third party devices on RS-232 (IR, AV).
-Streaming camera.
-Data logger with trends.
-BACnet certified BACnet Application Specific Controller (B-ASC).

-Luminaire monitoring for Motus DALI emergency, connected to the KNX/DALI gateway code PC68, appropriate programming and software. Contact iGuzzini for more details on the specific system configuration.

Technical data:
Power supply voltage: 24 V DC.
Energy consumption: 2 W.
LED 1 indicator: Green LED (CPU load). LED 2 indicator: Green LED (operating) or red LED (Reset).
Interface: 1 KNX, 1 10BaseT/100BaseTX, 1 RS-485 (including unterminated 47 K Ohm polarisation resistors).
1 RS-232, 1 USB2.0, 1 reset button.
Dimensions
General (mm) 58x52x90
Technical performance
  • Class III

    Class III

  • Protected against penetration of solids larger than 12 mm, not protected against penetration of liquids.

    Protected against penetration of solids larger than 12 mm, not protected against penetration of liquids.

Complies with EN60598-1 and pertinent regulations

Physical properties
Weight (kg) 0.09

Electrical data

Power Supply Electronic Power supply not included
Mounting options Remote
Control KNX

Installation

Description

Device width: 3 DIN modules (~54 mm);
Wiring Terminals:
Bus KNX: 2x0,8 mm² bus connection terminal
Power supply: terminal, 0.5 mm²–1.5 mm²
Serial: terminal, 0.5 mm²–1.5 mm²

Notes

Operation: -5 ... +45 °C
Max humidity: 93%, without condensation
Environment: can be used at heights of up to 2000 m above sea level (SLM)
Dimensions: 90 x 52 x 58 mm (HxWxD)