MI18
Colour
Technical Data
last update: 04/11/2025Description
1-gang actuator with two inputs. The two floating contacts can be connected to the two inputs. The first input is assigned to the actuator in the factory and allows immediate operation without the need for programming. Connection to 230V with flexible cable, approx. 20 cm long. The inputs and the KNX bus are connected with 6 wire cable, approx. 30 cm long. The connecting cable for the inputs can have a maximum length of 5 m. KNX software functions: Switching actuator functions:
operation as break/make contact. Behaviour in the event of bus power fault and recovery. Switch on/off delay. Timing function. Switching. Status feedback function. Logic combination. Disable function or priority control. Possibility of inverting the subject of the
status feedback function.
Binary input function:
Switching, dimmer, Venetian blind and regulator functions freely programmable. Block function.
Behaviour upon recovery of bus voltage.
Switching: two switching functions per input. Command on leading/trailing edge (ON, OFF, STEPPING, no signal).
Dimmer: Single surface or dual surface. Interval between dimmer dimming and switching and dimming values. Repetition of telegrams and end of telegram transmission. Venetian blinds: Command on leading edge (none, UP, DOWN, STEPPING), Operating principles (Step - Move - Step or Move - Step). Differentiation between short and long operation. Slat adjusting time.
East input, regulator and scenes: Edge (key for operation as break contact, key for operation as make contact, switch) and value above/below limit value. Adjusting value with key long-press. External scenes unit with save function.
Rated voltage: 230V AC
Rated current: 16 A, ohmic load
Switching contact: Break contact, relay floating contact
Rated output Incandescent lamps: 230V AC,
max. 2500 W
Halogen lamps: 230V AC, max. 2200 W
LV halogen lamps: max. 1000 VA, wound transformer max. 1000 W, dimmable electronic transformer
Capacitive load: 230V AC, 10 A, max. 105 μF
Inputs: 2
Temperature range: from -5 °C to 45 °C
Technical performance
Complies with EN60598-1 and pertinent regulations
Physical properties
Weight (kg)
0.2
Electrical data
Power Supply
Electronic Power supply not included
Mounting options
Remote
Control
KNX
Installation
Notes
For mounting in common double boxes or boxes for electronics (Kaiser type). Leave a minimum space of 4 mm between the 230V connection and the KNX/Inputs connection (SELV safety extra low voltage)