Region and Language

Product standard

Your language

E179

Downloads

Colour

Technical Data

last update: 09/02/2026
Description
Recessed emergency lighting luminaire with a symmetrical anti-panic optic (open area). 3 h autonomy with 12 h recharging time for maximum capacity. Self-test function. Test function via button on front, accessible when product is installed. Test function that can be activated via a Laser pointer. Built-in red/green LEDs for indicating different device states. Latest generation LiFePO4 (Lithium Iron Phosphate) 6.4 V 1.5 Ah battery. Power in non maintained mode: 0.52 W - Power in maintained mode: 3.5 W - Centralised on/off command module available on request for 150 or 250 luminaires (for this function further cabling with 2 conductors is required)
Dimensions
Diameter (mm) ø90
Shape Round
Recessed hole dimensions (mm) ø72
Technical performance
  • Class II

    Class II

  • Protected against penetration of solids larger than 12 mm, not protected against penetration of liquids.

    Protected against penetration of solids larger than 12 mm, not protected against penetration of liquids.

  • Protected against the penetration of solids larger than 1 mm, protected against the fall of water at a maximum angle of 15° <br /> On the visible part of the product once installed

    Protected against the penetration of solids larger than 1 mm, protected against the fall of water at a maximum angle of 15°
    On the visible part of the product once installed

  • Protected against 0,5 J shocks

    Protected against 0,5 J shocks

Complies with EN60598-1 and pertinent regulations

Physical properties
Material Thermoplastic
Product certification
  • CE
    CE
  • NOM
    NOM

Photometric data

Details

lm system
219.58
W system
3.4
Luminous efficiency - lm/W (system value)
64.58
lm in emergency mode
220
Maximum intensity (cd)
60
Light output ratio (LOR)
100
Optic and beam angle
Optics for Antic-Panic
Adjustability
fixed
Light colour quality
CRI 80
Colour temperature
5000 K
Lifetime LED 1
> 50,000h - L70 (Ta 25°C)

Charts and polar curves

Electrical data

Voltage 220 - 240
ZVEI code LED
Power Supply Electronic with inverter Driver included
Mounting options Integral

Installation

Description

On panels between 1 and 30 mm thick. Drill hole for installation between Ø 70-75 mm. The control electronics and batteries can pass through the hole. Minimum height above plasterboard: 90 mm.;
Mounting Ceiling recessed
Wiring 2 cabling options: non maintained (SE) or maintained (SA) requires 2 conductors (N/L). The operating mode is selected via a dip-switch. Maintained switching via a switch requires 3 conductors (N/L/L1). Cannot be used as a general lighting luminaire.

Notes

CCT 5000K (4250÷5350K)
Subscribe