Region and Language

Product standard

Your language

The North America market website will be available by November 2025. After clicking the 'Update' button, you will be redirected to the legacy version of the website. Le site Web du marché nord-américain sera disponible d'ici novembre 2025. Après avoir cliqué sur le bouton « Mettre à jour », vous serez redirigé vers le legacy version du site Web.
Update Update

MU31

Downloads

Colour

Technical Data

last update: 21/10/2025
Description
Luminaire with LED lamp for indicating escape routes. Ceiling-recessed installation. Body frame with white finish, shaped steel, perimeter surface edging. Plastic component holder box. Permanent operation (always on - SA); in event of blackouts guarantees an emergency autonomy of 3 hours with the battery fully charged. Sign visible from a distance of 25m (in compliance with UNI EN 1838). Self-test mode. LED warning lamp with function that indicates which devices are operating correctly and if there are any faults. For explanations of all the operating warning lamp functions, see the instructions sheet. Ni-Cd battery with 24 hour recharge time. Indicator screens available with a separate code (pictogram design L22).
Dimensions
General (mm) 310x50x82
Recessed hole dimensions (mm) 312x53
Technical performance
  • Class I

    Class I

  • Protected against the penetration of solids larger than 1 mm, protected against the fall of water at a maximum angle of 15°

    Protected against the penetration of solids larger than 1 mm, protected against the fall of water at a maximum angle of 15°

Complies with EN60598-1 and pertinent regulations

Physical properties
Material Metal and technopolymer
Product certification
  • CE
    CE
  • ENEC-03
    ENEC-03

Photometric data

Details

lm source
35
W source
1
lm in emergency mode
-
Optic and beam angle
D - Diffused light
Adjustability
fixed
Light colour quality
CRI (minimum) 80
Colour temperature
4000 K

Electrical data

Voltage 220 - 240
ZVEI code LED
Power Supply Electronic with inverter Control gear included
Mounting options Integral

Installation

Description

Ceiling-recessed - by inserting the device into the relative slot using the steel wire spring, compatible with false ceilings between 10 and 30 mm thick.;
Mounting Ceiling recessed
Wiring Inside the structure - the protection panel must be removed and the necessary connections made on the standard terminals.

Notes

Rest Mode function: allows the system to be switched off for short periods. The emergency system must be reactivated using the remote control (code no. MXT0).